Permit Number: T21CM09048
Parcel: 115180280

Address:
1500 N 15TH AV

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM09048
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide information for the natural gas piping system as requested on the gas piping template. Include a natural gas schematic showing the pie sizes, appliance gas loads and the developed lengths of the piping from the gas meter to each appliance. Reference: Section 107.2.1, IBC 2018 and Sections 402.1 and 402.3, IFGC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/22/2021 NGARCIA3 OUT TO CUSTOMER Completed