Review Details: COMMERCIAL - TI
Permit Number - T21CM09009
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/26/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 12/02/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 12/08/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 12/14/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/15/2021 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 12/17/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Provide a detailed description of the scope of work. 1 . Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements |