Permit Number: T21CM09004
Parcel: 14043013D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM09004
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2021 SBLOOD1 ENGINEERING REVIEW Passed
12/01/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Passed
12/06/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/08/2021 JPEELDA1 FIRE REVIEW Approved
12/14/2021 STEVE SHIELDS ZONING REVIEW Approved
12/14/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/17/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 . Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Include; (A) AIC ratings and secondary conduit, conductor sizes and types on the line diagram. (B) Complete panel schedule, voltage, phase, amp and AIC ratings, all OPCD’s ratings, main breaker or main lug only , load calculations. (C) Locate the 200 amp service and sub- panel on the site plan.

Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements