Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM09004
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/26/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 12/01/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 12/06/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 12/08/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 12/14/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/14/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/17/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 . Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Include; (A) AIC ratings and secondary conduit, conductor sizes and types on the line diagram. (B) Complete panel schedule, voltage, phase, amp and AIC ratings, all OPCD’s ratings, main breaker or main lug only , load calculations. (C) Locate the 200 amp service and sub- panel on the site plan. Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements |