Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM08967
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/26/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 11/26/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 11/30/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheets Index through ID3.1: These sheets require a seal, signature, and date of the architect in responsible charge. |
| 12/02/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The increased exhaust flow rate for the building likely exceeds the minimum ventilation requirement for office occupancy. Show that the total amount of ventilation air introduced by the existing HVAC units is sufficient to supply the air required for transfer to the restrooms, laundry room, and for ventilation of the other spaces being served by the HVAC units. Reference: Sections 403.2.2 and 501.4, IMC 2018. |
| 12/02/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the size of the gas pipes serving the two existing furnaces. Based on the demand and developed pipe length for each appliance, a ¾" pipe is required for both units. Reference: Sections 402.1 and 402.3, IFGC 2018. |
| 12/02/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/13/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM08967 2488 N Palo Verde Ave – R-3 Commercial Office Improvements (1st Review) TRANSMITTAL: December 13, 2021 This site is located in the R-3 zone (UDC 4.7.12). Commercial Office is not an allowed use in the zone. 1. It appears that the proposed office is part of a residential care facility. If so provide approved documentation for the residential care facility and that it meets any applicable UDC Use Specific Standards. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
| 12/13/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/15/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |