Permit Number: T21CM08958
Parcel: 133350040

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM08958
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved. The plumbing schematic shows the two fixtures with a common vent and a single horizontal drain leading to the existing building drain. Revise the plumbing plan to match the schematic. [Second comment: Comment not addressed. The plumbing schematic and the plumbing plan still show two different piping layouts.] [Initial comment: Coordinate the plumbing schematic with the plumbing plan. If the plumbing schematic is correct, there will only be one horizontal drain, not two, and a cleanout will be required. Reference: Sections 708.1, 909.1, and 911, IPC 2018.]