Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM08958
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not resolved. The locations of the required cleanouts cannot be evaluated until the design of the waste piping is coordinated (item #2). [Initial comment: Show all code-required cleanouts and the vents. Reference: Section 107.2.1, IBC 2018.] 2. Comment not addressed. The plumbing schematic and the plumbing plan still show two different piping layouts. [Initial comment: Coordinate the plumbing schematic with the plumbing plan. If the plumbing schematic is correct, there will only be one horizontal drain, not two, and a cleanout will be required. Reference: Sections 708.1, 909.1, and 911, IPC 2018.] |