Permit Number: T21CM08958
Parcel: 133350040

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM08958
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved. The locations of the required cleanouts cannot be evaluated until the design of the waste piping is coordinated (item #2). [Initial comment: Show all code-required cleanouts and the vents. Reference: Section 107.2.1, IBC 2018.]
2. Comment not addressed. The plumbing schematic and the plumbing plan still show two different piping layouts. [Initial comment: Coordinate the plumbing schematic with the plumbing plan. If the plumbing schematic is correct, there will only be one horizontal drain, not two, and a cleanout will be required. Reference: Sections 708.1, 909.1, and 911, IPC 2018.]