Permit Number: T21CM08958
Parcel: 133350040

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM08958
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2021 SBLOOD1 ENGINEERING REVIEW Passed
11/26/2021 JVINCEN1 FIRE REVIEW Approved
11/30/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/01/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/01/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show all code-required cleanouts and the vents. Reference: Section 107.2.1, IBC 2018.
2. Clarify what is occurring with the two horizontal drains near the bag-in-box. Where is the existing building drain? Is that third floor sink by the bag-in-box? Reference: Section 107.2.1, IBC 2018.
3. Coordinate the plumbing schematic with the plumbing plan. If the plumbing schematic is correct, there will only be one horizontal drain, not two, and a cleanout will be required. Reference: Sections 708.1, 909.1, and 911, IPC 2018.
4. Indirect waste receptors shall not be installed in concealed spaces. Provide ready access to the waste receptor. Reference: Section 802.4, IPC 2018.
12/01/2021 ROBERT SHERRY WATER REVIEW Completed
12/13/2021 STEVE SHIELDS ZONING REVIEW Approved
12/13/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/15/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved