Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM08927
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/30/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S-501.00; Detail 101A: Please indicate the length of the steel column embedment into the spread footing, or the clear distance of the bottom of the steel column to the bottom of the footing. 2. General: This is a commercial project and therefore requires a registered design professional (or professionals) to stamp all submitted sheets per the 2018 IBC Section 107.1. 3. General: The structural drawings must include Structural General Notes, Material Strengths, Required Special Inspections, Soil Bearing Values, Design Loadings, etc. as required for construction. 4. General: Please provide written responses to all review comments. |
| 12/08/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | This is a commercial project and therefore requires a registered design professional (or professionals) to stamp all submitted sheets per the 2018 IBC Section 107.1. |
| 12/13/2021 | SSHIELD1 | ENGINEERING | REVIEW | Reqs Change | See Zoning comments |
| 12/13/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM08927 333 W Ajo Wy – C-2 Shade Structure w/Solar (1st Review) TRANSMITTAL: December 2, 2021 This site is located in the C-2 zone (UDC 4.7.21). 1. Per UDC Article 3.3.3.G.2.c when structure additions are proposed a development package is required. A development package (DP) meeting the requirements of the checklist for Minor Changes to a Commercial/Industrial Site found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf, shall be submitted and approved prior to approving this building plan. A The DP is a separate submittal from the building plan and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/13/2021 | VVERA1 | OUT TO CUSTOMER | Completed |