Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM08894
Parcel: 136230400

Address:
3401 S BIRCH AV

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM08894
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM08894
Roof top Solar Panels (1st Review)
3401 S BIRCH AV

TRANSMITTAL DATE: December 7, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: Provide manufacturer specification sheets for collector panels, inverter and mounting hardware on the next submittal.

COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2021 VVERA1 OUT TO CUSTOMER Completed