Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM08847
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2021 SBLOOD1 ENGINEERING REVIEW Passed
11/23/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM08847
1445 E Linden St – NR-1
Master Suite Addition (1st Review)

TRANSMITTAL: November 23, 2021

COMMENTS: the following comments are relative to an application for NPZ Review (UDC 5.10.3).

This site is located in the NR-1 zone (UDC 5.10.3). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

Prior to zoning approval an NPZ review and approval is required. Owner is proposing to construct a master suite addition to the rear of the existing dwelling. The property fronts on two local streets Linden and Vine. Structure meets setbacks and is considered to be facing the side street perimeter yard.

NPZ is a separate submittal from the building permit. Application for the NPZ can be found at: https://www.tucsonaz.gov/files/integrated-planning/Special_Districts_Application_Revised_9-10-21_fillable.pdf, and is submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Special Districts”. Contact for questions about NPZ review is Nicholas Martell, Nicholas.Martell@tucsonaz.gov.
11/23/2021 SSHIELD1 NPPO REVIEW Passed
12/09/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM08847
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF. Update detail A on sheet A3.1.

PLUMBING PLANS:

1. Provide devices rated for application, G2406.3. A two-way water valve is not appropriate for building drainage. Remove the diverter valve or provide the spec sheet for a compliant diverter for drainage applications.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review