Permit Number: T21CM08842
Parcel: 112033980

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM08842
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
03/03/2022 WBERGER1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T21CM08842
2518 E Richards Pl
Replace Carport with Garage & Laundry Room and Remodel Kitchen (2nd Review)

TRANSMITTAL DATE: 03/03/2022

COMMENTS: The following comments are relative to either an application for a Design Development Option (DDO) (UDC 3.11.1) or a Board of Adjustment variance (UDC 3.10.3).

This site is in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to use-specific standards 4.9.7.B.5-9.

1. The correct zoning is R-1 and not R-2 as indicated on the plot plan.
2. Indicate the names of the owner and the legal description of the property on the plot plan.
3. The subdivision plat shows a five-foot wide aerial easement along the south property line. Either obtain written approval from Tucson Electric Power to maintain the existing location of the accessory structure or move the accessory structure away from the aerial easement.
4. Per UDC 6.4.5.C.1.a, the minimum required front street perimeter yard setback is the greater of 20'-0" or one and one-half the height of the proposed wall, measured from the street property line. Based on a wall height of less than 13'-4", the required front street perimeter yard setback is 20'-0"; proposed is 13'-0".

5. A DDO must be submitted and approved to reduce the required setbacks only if the garage is changed as a carport (UDC 6.4.5.C.2.b). The DDO application and its requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. The DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type "Zoning Administration." Please contact Mark Castro at Mark.Castro@tucsonaz.gov if you have questions about the DDO application or process.

6. If you do not wish to construct a carport rather than the garage, a variance would be required to allow the applicant to construct a garage 13'-0" from the front street perimeter yard lot line. For more information on the variance process, please refer to the following: https://www.tucsonaz.gov/files/pdsd/codes/Zoning_Administration_Application_BA_fillable.pdf. Please contact Mark Castro at Mark.Castro@tucsonaz.gov if you have questions about the DDO application or process.

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or at 520-837-4951.