Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM08823
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/31/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/16/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM08823 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Conditionally Approved ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Denied SECOND REVIEW: 1 THRU 4 OK 5). ADDED TRAP PRIMER VALVE DETAIL ON P630 NEEDS A COLD WATER SHUT OFF VALVE. -IPC 606.2 6 THRU 9 OK 10). ADDED REQUIRED HIGH/LOW DRINKING FOUNTAIN NEEDS A SANITARY VENT AND WATER CONNECTION UPDATE P-620 & P-621. -IPC A106.3.1 , 604.5, 901.2.1 |
| 02/24/2022 | LBOWERS1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Reqs Change | PER PC ADDRESSING THIS PROJECT REQUIRES A SUITE NUMBER. PLEASE CONTACT ADDRESSING TO HAVE SUITE NUMBERS ASSIGNED. PLEASE SUBMIT PLANS TO PC ADDRESSING TO HAVE SUITE NUMBER ASSIGNED AND PAY FOR NEW UNIT NUMBERS. PLEASE SEND TO ADDRESSING @PIMA.GOV |