Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21CM08823
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/10/2021 | LBOWERS1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Reqs Change | PLEASE REACH OUT TO PC ADDRESSING TO DETERMINE IF SUITE NUMBERS NEED TO BE ASSIGNED BASED ON THE ADDTIONAL USE. 520-724-9512 ADDRESSING@PIMA.GOV. |
| 11/26/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 11/26/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM08823 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Provide accurate information regarding Current Codes per International Building Code 2018. The information provided on submitted Enercalc Structural Calculations for wood beam 6.75x24 GLB is incorrect where IBC 2012 is referenced. Revise and resubmit. BUILDING REVIEW COMMENTS: Denied 1. The janitor closet door encroaches in the exit access more than is permitted. Provide a exit access that meets the requirements of Section 1005.7 2. The porter room door encroaches in the exit access more than is permitted. Provide a exit access that meets the requirements of Section 1005.7 MECHANICAL REVIEW COMMENTS: Conditionally Approved 1. Approved/subject to field approval ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Denied 1). Add gas piping sizing table used to plan pg. M-111. -IFGC 402.4 2). Add gas piping support detail to plan pg. M-612 or P-630. IFGC A106.31 3). Add gas equipment connection detail to plan pg. M-621 orP-630 -IFGC A106.3.1 4). P2 Lav on plan pg. P-630 fixture schedule needs to include the required ASSE 1070 mixing valve information. IPC A106.3.1 & 419.5 5). Add floor drain Trap primer detail to P-630. IPC A106.3.1 6). Add piping materials for gas, gravity sanitary, & forced sanitary to plan pg. P-111. IPC A106.3.1 7). Hot water system needs 1" insulation update Plan pg. P-111. IPC 607.2.1 607.5 8). Water dispenser is shown on Plan pg. P-621 but not listed on P-630 fixture schedule. -IPC A106.3.1 9). Water dispenser connection requires an ASSE 1022 or 1024 backflow preventer. -IPC 608.17.1.2 10). This occupancy type & load requires a high/low drinking fountain. plan pg. D-111E only shows single level type. -IPC 403.1 & 410.3 |
| 12/01/2021 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the size of the water meter, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018. |
| 12/02/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/02/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/21/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/21/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |