12/02/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM08815
Roof top Solar Panels (1st Review)
6210 E 2ND ST

TRANSMITTAL DATE: December 2, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: COMMENT: After comparing the aerials to the plot plan it has come to my attention that there is a possible non-permitted porch addition on the South portion of the house. After researching PRO there were no records for the porch addition that could be verified or found. If no permits are available relocate the solar panel away from the porch structure or a permit must be obtained for the porch addition.

COMMENT: Provide manufacturer specification sheets for collector panels, inverter and mounting hardware on the next submittal.

COMMENT: Since the panels are going to be placed on two separate structures and one service shall continue to serve both structures, it is essential that all equipment and systems can be easily isolated at each building. Demonstrate how the equipment is going to be isolated by each structure.

COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
.