Review Details: COMMERCIAL - TI

Permit Number - T21CM08812
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-1 (Demolition Floor Plan); Sheet A-1 (Proposed Floor Plan): The Demolition Floor Plan indicates 8 existing water closets, 2 existing urinals, and 6 existing lavatories in the restroom area to be removed. The Proposed Floor Plan indicates 2 new water closets and 2 new lavatories are to replace the removed fixtures. From the Site Plan on Sheet SD-1, it appears these restrooms could serve occupants not only in the Committee Building, but also from the bleachers, animal pens, Press Media Building, Staging Area, and Lion's Building. Please verify with calculations on the drawings the plumbing fixtures provided in this building meet the requirements of the IBC Table 2902.1 and Section 2902.3.3 for water closets and sinks in this area.
2. Sheet A-1; Wall Legend: For New Walls (Interior), please indicate the metal stud gauge required.
3. Sheet A-1; Wall Legend: The New Walls (Interior) reference Details 5/A2 and 6/A2. Please revise those references.
4. Sheet A-1; Proposed Floor Plan: The interior plumbing wall at the new restrooms is a 6" wall. There are no wall studs listed in the Wall Legend for a 6" wall. Please provide.
5. Sheet A-1; Proposed Floor Plan: A section cut on the west wall at the work counter references 6/A2. Please revise that reference.
6. General: Please provide written responses to all review comments.
11/23/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/23/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The plumbing demo drawing shows six water closets and two urinals being eliminated. Verify that sufficient plumbing fixtures are available for the population in that part of the rodeo grounds (i.e. plumbing fixtures available within a travel distance of 500-feet). Reference: Sections 403.1 and 403.3.3, IPC 2018.
2. Provide information to show how the proposed water heater is to be anchored to the building structure, as noted in detail 201 (nothing shown on the architectural drawings). Reference: Section 301.2, IPC 2018.
11/23/2021 ROBERT SHERRY WATER REVIEW Completed
11/30/2021 IMONSHI1 ZONING REVIEW Approved
11/30/2021 IMONSHI1 ENGINEERING REVIEW Passed
11/30/2021 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
12/02/2021 JPEELDA1 FIRE REVIEW Approved Plans shall show the structure in proximity to the building. Show the width of the road with the new structure.

Questions:
Jennifer Peel-Davis
520-837-7033
Jennifer.Peel-Davis@Tucsonaz.gov
12/02/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/02/2021 JPEELDA1 FIRE REVIEW Approved notes for the wrong permit were added.