Permit Number: T21CM08810
Parcel: 11621302C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM08810
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2021 SBLOOD1 ENGINEERING REVIEW Passed
11/18/2021 JVINCEN1 FIRE REVIEW Approved
11/22/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G0.0; Governing Codes: The ICC/ANSI A117.1 indicates the 2015 Edition. Please revise that to the 2009 Edition.
2. Sheet G0.0: Please provide a Project Narrative on this sheet. Indicate if new X-ray equipment is to be provided under this permit, and if the new equipment is to be floor or ceiling mounted. If new equipment is to be ceiling mounted, please provide structural calculations and details of the equipment supports and connections to the existing structure, and the adequacy of the existing structure to support the new equipment.
3. Sheet G0.1; Code Review: This title indicates the 2012 IBC. Please revise that to the 2018 Edition.
4. Sheet A1.0; Floor Keynotes: In note 2 ("New Wall"), please indicate the wall stud size, gauge (if metal studs), and spacing.
5. General: Please provide written responses to all review comments.
11/23/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/23/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/23/2021 ROBERT SHERRY WATER REVIEW Completed
12/01/2021 NMARTEL1 ZONING REVIEW Approved
12/01/2021 NMARTEL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/07/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved