Permit Number: T21CM08806
Parcel: 135103290

Address:
7350 E 33RD ST

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM08806
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2021 IMONSHI1 ENGINEERING REVIEW Passed
12/06/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed
12/06/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM08806
7350 E 33rd St – R-1
Shade Structure w/Solar (1st Review)

TRANSMITTAL DATE: December 6, 2021

This site is located in the R-1 zone (UDC 4.7.8). A single family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9.

1. The property dimensions shown on the plot plan do not match what is shown on Manana Grande Plat recorded at Bk 14, Pg 70.

2. Provide a lot coverage calculation that meets the requirement of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf, and provide a correct lot coverage calculation.

3. Provide the zoning for this parcel and all adjacent parcels on the plot plan.

4. Per UDC Article 6.6.3C the maximum height of a detached accessory structure is 12’ as measured from design grade to the mid-point of a pitched roof, see UDC Article 6.4.4. Provide a height dimension from the mid-point of the pitched roof to design grade.

5. Per UDC Table TABLE 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 ZONES, R-1 Zone, Res-Use to Res-Zone the required interior perimeter yard setback is 6’-0” or 2/3 the height of the exterior wall. Per UDC Article 6.4.5.B.2 for structures like the perimeter yard setback is measured to the post supporting the roof structure as long as the roof overhang does not exceed 2’-0”, see UDC Article 6.4.5.D.1.b. That said based on a wall height of 14’-7” the required perimeter yard setback from the proposed structure to the west property line is 9’-9”, proposed setback using the allowed 2’-0” overhang is 8’-9”. As this is a detached accessory structure a neighbor’s setback waiver maybe used to reduce the perimeter yard setback. To obtain this waiver the following statement must be provided on the plot and then be signed and dated by the adjacent property owner:
My Name is____________________ and I am the owner of the property located at_______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan.

Signature: _____________________________

Date: _________________________________
If the setback waive cannot be obtained the structure will either need to be relocated to meet required perimeter yard setbacks of a Deign Development Option (DDO) will need to be submitted and approved.

If you have any questions about this transmittal, please contact Elisa Hamblin at ElisaHamblin@tucsonaz.gov.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/06/2021 NGARCIA3 OUT TO CUSTOMER Completed