Permit Number: T21CM08751
Parcel: Unknown

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM08751
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM08751
Roof top Solar Panels (1st Review)
5463 S MINORKA PL

TRANSMITTAL DATE: November 30, 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments


COMMENT: Since the plan are being place on a manufactured home a engineered sealed plan is required


COMMENT: Residential will review the application on the next submittal

COMMENT: Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and conductor) rating, NEC 690.64 & 705.12 (D). Show the backfeed breaker incompliance with the bus limitation or increase the service panel rating.

If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/30/2021 NGARCIA3 OUT TO CUSTOMER Completed