Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM08722
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/29/2021 | PCAMARE1 | OIP | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Residential Review Section PROJECT: T21CM08722 Roof top Solar Panels (1st Review) 202 W VETERANS BL TRANSMITTAL DATE: November 29, 2021 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments COMMENT: This plan set is not compliant with the Fire code, demonstration compliance to 2018 International Fire Code 1204.2.1.1. If the slope of the building is greater than 2:12 then compliance must be shown on the plans. Show a 36” wide access pathway from the eave to the ridge on both sides of the building. COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans . |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/29/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |