Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T21CM08683
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/09/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments and provide a written response. The plans submitted are dated in the year 1998, and there are no registrant stamps. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Please update the plans. Provide a detailed description of the scope of work to be performed. Include all work associated with the electrical building service(s), and downstream wiring for power and lighting Ref; 2018 IBC section 107.1.2, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/09/2021 | NGARCIA3 | OUT TO CUSTOMER | Completed |