Permit Number: T21CM08676
Parcel: 120073220

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM08676
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2021 WBERGER1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T21CM08676
376 W District St
Master Suite Addition (1st Review)

TRANSMITTAL DATE: November 12, 2021

COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC Section 3.11.1).

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6, .9, & .10.

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the wall; see Unified Development Code (UDC) Section 6.4.5.b & Figure 6.4.5-A.

The minimum required setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 11'-2", the required perimeter yard setback from the proposed addition to the east property line is 7'-5"; proposed is 6'-0".

The DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type "Zoning Administration." If you have questions about the DDO application or process, please contact Mark Castro at Mark.Castro@tucsonaz.gov.

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or at (520)837-4951.
11/12/2021 WBERGER1 ENGINEERING REVIEW Passed
12/03/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM08676
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Show the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Identify the utility lines requiring upgrade or replacement. Include an existing or upgraded 1” line to the building, P2903.7.

ELECTRICAL PLANS:

1. Show a smoke alarm in each bedroom and outside in the immediate vicinity, R314.3.
2. Show one 20 AMP branch circuit in the laundry area; this circuit may not serve other locations, E3703.3 and 3901.8. Replace MP-2 at the clothes washer.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review