Permit Number: T21CM08661
Parcel: 128100770

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM08661
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Passed
11/17/2021 SBLOOD1 ENGINEERING REVIEW Passed
11/24/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/24/2021 STEVE SHIELDS ZONING REVIEW Approved
11/26/2021 JVINCEN1 FIRE REVIEW Approved
12/02/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Show the location of the electrical service on the site plan. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements