Permit Number: T21CM08648
Parcel: 129150020

Address:
1702 S EUCLID AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM08648
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets BOM through SPEC-2: All drawing sheets must be sealed, signed, and dated by the engineer of record.
2. General: Please provide a Special Inspections Certificate with Parts A and B completed for bolts in concrete, high strength bolts, and epoxy anchors. This form can be found at www.tucsonaz.gov/PDSD.
11/29/2021 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/29/2021 NGARCIA3 OUT TO CUSTOMER Completed