Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T21CM08639
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/10/2021 | NMARTEL1 | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL Nicholas Martell, Planner T21CM08639 Residential Addition November 10, 2021 The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed. 1. The side perimeter yard setback in the R-1 zone is 6' or 2/3 the height of the structure, whichever is greater. Based on a wall height of 10'-8", the minimum required perimeter yard setback to the NORTH lot line is 7'-2". Additionally, the required front street setback is 20' as measured to the EAST lot line. A Design Development Option (DDO) would be required to reduce the side and front perimeter yard setbacks. The application can be found here: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. Please add a response letter addressing each comment. If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov |
| 11/10/2021 | NMARTEL1 | ENGINEERING | REVIEW | Passed | |
| 12/01/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Indicate the location of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Show all utility point of connections. Include an existing or upgraded 1" line for total building demand, P2903.7. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF. Show a circuit or gas pipe sized for operating the water heater. Show a dryer vent to the exterior. |