Permit Number: T21CM08639
Parcel: 136330610

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM08639
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T21CM08639
Residential Addition
November 10, 2021

The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.

1. The side perimeter yard setback in the R-1 zone is 6' or 2/3 the height of the structure, whichever is greater. Based on a wall height of 10'-8", the minimum required perimeter yard setback to the NORTH lot line is 7'-2". Additionally, the required front street setback is 20' as measured to the EAST lot line. A Design Development Option (DDO) would be required to reduce the side and front perimeter yard setbacks. The application can be found here: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. Please add a response letter addressing each comment. If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
11/10/2021 NMARTEL1 ENGINEERING REVIEW Passed
12/01/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Indicate the location of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Show all utility point of connections. Include an existing or upgraded 1" line for total building demand, P2903.7.

An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF.

Show a circuit or gas pipe sized for operating the water heater.

Show a dryer vent to the exterior.