Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM08631
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/11/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheets G001, A100 through A502: This is a commercial project, therefore the requirements of the IBC Section 107 must be met. Please provide a seal, signature, and date by a registered design professional on these sheets. 2. Sheet G001; Sheet List: Please include all sheets included in this submittal in the Sheet List. 3. Sheet A100: Please provide a Code Analysis on this sheet, indicating applicable codes, occupancy classification, construction type, actual square footage of the addition, allowable square footage for all buildings combined, occupancy load of the addition, occupancy load for all buildings combined, plumbing fixtures required for all buildings combined, exit requirements, egress requirements, and accessibility requirements. 4. Sheet A100; Setbacks From Property Lines: The setbacks all indicate 0'. Please revise. 5. General: Please provide a Special Inspections Certificate with Parts A and B completed. This can be provided by the structural engineer for the next submittal. 6. General: Please provide written responses to all review comments. |
| 11/16/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 11/16/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide secondary (overflow) roof drainage. Reference: Sections 1108.1, 1108.2 and 1108.3, IPC. |
| 11/16/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Sheets G001, A100 through A502: This is a commercial project, please provide a seal, signature, and date by a registered design professional on these sheets. Sheet A100: Please provide a Code Analysis on this sheet, indicating applicable codes, occupancy classification, construction type, actual square footage of the addition, actual square footage of the existing, allowable square footage for all buildings combined, occupancy load of the addition, occupancy load for all buildings combined, plumbing fixtures required for all buildings combined, exit requirements, egress requirements, and accessibility requirements.Provide information regarding fire sprinklers and fire alarm systems. Provide distance from existing fire hydrant to the furthest part of the building and a diagram showing as the hose lays not crow flys. General: Please provide written responses to all review comments. Questions: Jennifer Peel-Davis 520-837-7033 Jennifer.Peel-Davis@Tucsonaz.gov |
| 11/16/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/23/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM08631 31 E Rillito St – I-1 Garage Addition TRANSMITTAL: November 23, 2021 This site is located in the I-1 zone (UDC 4.7.29). 1. Per UDC Article 3.3.3.G.2.c a Development Plan (DP) is required to be submitted and approved for this project prior to approval of this building plan. The DP shall meet the requirements of the Administrative Manual 2-06. The DP is a separate submittal from the building permit and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
| 11/23/2021 | SSHIELD1 | ENGINEERING | REVIEW | Reqs Change | See Zoning comments |
| 11/23/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/24/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed |