Permit Number: T21CM08623
Parcel: 14118008P

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM08623
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM08623, T21CM08621, T21CM08622

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
N/A


PLUMBING REVIEW COMMENTS:
Denied
Third Plumbing Review:
1 thru 8 OK
9). SAME-Now that a site utility piping plan has been provided, the water service entrance location on plan pages A0.1 & P1 don't correlate. -IPC A106.3.1 **see note #9 on P1 the potable water entrance location doesn't match site plan water main entrance locations on A0.1, also Plan P1 shows 2 sewer exits plan page A0.1 only shows 1** pages need to correlate.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/03/2022 STEVE SHIELDS ZONING REVIEW Approved