Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM08623
Parcel: 14118008P

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM08623
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2021 JVINCEN1 FIRE REVIEW Approved
11/22/2021 ROBERT SHERRY WATER REVIEW Completed
11/22/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM08621, T21CM08621 & T21CM08621,
10042 E Old Vail Rd – PAD-36
Medical Office (1st Review)

TRANSMITTAL: November 22, 2021
This site is located in the PAD-36, medical office use is allowed in the PAD.

1. The building plans have been reviewed for compliance with DP21-0263 and although it appears that the plans match until DP21-0263 has been approved Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
11/22/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM08621 - 8623

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. The Geotechnical Report submitted references International Building Code 2012. Provide accurate information regarding Current Codes per International Building Code 2018. The information provided is incorrect since State has adopted latest Codes.

BUILDING REVIEW COMMENTS:
Denied
1. No egress plan provided. Provide a thorough egress plan indicating travel distances and applicable requirements.
2. The occupant load provided is incorrect. Provide a thorough occupant load calculation. Include a room by room occupant load calculation and separate the tenant space occupant loads.
3. Separate the square footages for the tenant spaces.


MECHANICAL REVIEW COMMENTS:
Approval Pending
1. Approved/subject to field approval


PLUMBING REVIEW COMMENTS:
Denied
1). Add overflow scupper detail to plan pg. A1.1. design needs to comply with IPC 1108.1
2). Add scupper & roof drain sizing calculations to plan pg. A1.1, calculations need to derive from IPC 1106.2 thru 1108.3
3). Add roof drain piping illustrations to the plumbing pages. - IPC A106.3.1
4). P9 water dispenser on plan pg. P3 can't substitute for the required high/low drinking fountain due to occupancy type & load. update all affected pages. -IPC 403.1 & 410.3
5). Notate on fixture schedule item P8 on plan pg. P3 if the washer is commercial or residential type. If commercial type a lint interceptor will be required. -IPC 1003.6 see exception #2
6). Add an ASSE 1022 or 1024 backflow preventer to Item P10 on plan pg. P3 fixture schedule. -IPC 608.17.1.2
7). Add restroom lavatory sidewall fixture spacing measurement to plan pg. A0.3 or A4.2 -IPC 405.3.1
8). Show calculations that a 1" meter can supply the water demand of a 2" main to this tenant & the multiple future tenants. or match the system size -IPC 603.1
9). Supply a site utility piping plan to see that continuation of the storm, water & sanitary sewer correlate with the building stub out locations & sizes. - IPC A106.3.1
11/22/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/08/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/09/2021 VVERA1 OUT TO CUSTOMER Completed