Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM08622
Parcel: 14118008P

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM08622
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM08621, T21CM08622, T21CM08623

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
N/A


PLUMBING REVIEW COMMENTS:
Denied
Third Plumbing Review:
1 thru 8 OK
9). SAME-Now that a site utility piping plan has been provided, the water service entrance location on plan pages A0.1 & P1 don't correlate. -IPC A106.3.1 **see note #9 on P1 the potable water entrance location doesn't match site plan water main entrance locations on A0.1, also Plan P1 shows 2 sewer exits plan page A0.1 only shows 1** pages need to correlate.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/03/2022 STEVE SHIELDS ZONING REVIEW Approved