Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM08602
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/13/2021 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM08602 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Approval Pending Approved/subject to field approval ELECTRICAL REVIEW COMMENTS Approval Pending Reviewer Response: Accepted, because the design also included fused protection. If you need to rely on Series ratings you will need to call out and use the same manufacuterer for specifice series installations. Be aware that other reviewers will generally comment on this. Providing fault current calculation will result in no comments on this issue. PLUMBING REVIEW COMMENTS: Denied 2). SAME- Can't replace the High/Low drinking fountain with a bottle filler only. A High/low drinking fountain will need to be re-installed with or without a bottle filler attachment. Update P6 on fixture schedule on plan pg. P2.0 & Keynote #6 on P1.0 -IPC 410.3 410.4...... The Tucson amendment to 410.4 states "when a single drinking fountain is required it may be substituted with a point of use cooler or dispenser". IPC 410.3 requires a minimum of 2 drinking fountains be provided that comply with wheelchair & standing persons. The amendment would only apply to a single non ADA drinking fountains beyond the minimum requirement. |