Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM08601
Parcel: 12112401A

Address:
5326 E PIMA ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM08601
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/20/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Provide the civil plans showing the installation of the water service to the building as part of the building plan set. Reference: Sections 107.2.1 and 107.2.6, IBC 2018 [Initial comment: Show the location of the proposed water meter, backflow preventer, and the water service pipe. Reference: Section 107.2.1 and 107.2.6, IBC 2018.]
2. An approved development plan is not to be used for construction of on-site utilities. Provide the civil plans showing the installation of the building sewer as part of the building plan set. Reference: Sections 107.2.1 and 107.2.6, IBC 2018. [Initial comment: The maximum distance between cleanouts shall be 100-feet, measured along the developed pipe length (see sheet 2 of 5). Reference: Section 708.1.1, IPC 2018.]
3. An approved development plan is not to be used for construction of on-site utilities. Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.]
01/20/2022 ROBERT SHERRY WATER REVIEW Reqs Change Comment not addressed. [Initial comment: Reduced pressure backflow prevention assemblies are required at the water meter for apartment buildings that have common laundry facilities, irrigation systems that are served by the same meter that serves the building, and facilities with central HVAC equipment (e.g. boilers, chillers). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf.]
01/26/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/26/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM08601
5326 E Pima St – C-1
Multi-Family – Mixed Use

TRANSMITTAL: January 26, 2022
This site is located in the C-1 zone (UDC 4.7.20). Mixed use is allowed in the zone.


1. This comment was not addressed. The development package sheets are not the stamped set. The development package sheets provided in the building set either need to be the stamped approved sheets, marked for reference only or removed from the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
02/25/2022 JPEELDA1 FIRE REVIEW Approved