Address:
5326 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T21CM08601
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/09/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show the location of the proposed water meter, backflow preventer, and the water service pipe. Reference: Section 107.2.1 and 107.2.6, IBC 2018.
2. The maximum distance between cleanouts shall be 100-feet, measured along the developed pipe length (see sheet 2 of 5). Reference: Section 708.1.1, IPC 2018.
3. Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
11/09/2021 ROBERT SHERRY WATER REVIEW Reqs Change Reduced pressure backflow prevention assemblies are required at the water meter for apartment buildings that have common laundry facilities, irrigation systems that are served by the same meter that serves the building, and facilities with central HVAC equipment (e.g. boilers, chillers). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf.
11/16/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; General Notes: Note 1 indicates all construction shall conform to the 2018 IRC. This is a commercial building. Please revise the note to reference the 2018 IBC and verify all construction meets the requirements of the 2018 IBC..
2. Sheet A1; Code Review: Note 4 indicates the project was designed with the 2018 IRC. A triplex is considered a commercial building. Please revise the note to reference the 2018 IBC and verify all design meets the requirements of the 2018 IBC.
3. Sheet A1; Code Review: Per the IBC Section 420.4, an automatic sprinkler system is required in Group R occupancies. Please indicate this requirement and the sprinkler system type on this sheet.
4. Sheet A1; Code Review: Please indicate the occupant load for each unit, and list the total occupant load for the building on this sheet.
5. Sheet A1; Code Review: Per the IBC Table 1006.2.1, please indicate the maximum allowable common path of egress travel distance for this project and the actual travel distance on this sheet.
6. Sheet A1; Notes: Notes 3, 4, 5, and 6 reference the 2018 IRC. Please revise that reference to the 2018 IBC and revise the reference sections as required.
7. Sheet A2; Exit Requirements: Please indicate on the window openings a width of 20" net clear horizontal, a height of 24" net clear vertical, and a total minimum net clear opening area of 5.7 SF.
8. Sheet A4; Notes: Please remove all references to the IRC, and replace with the IBC.
9. Sheet A5; Notes: Please remove all references to the IRC, and replace with the IBC.
10. Sheet A6; Section 8: Please indicate the U.L. Listing Number for this wall assembly, or indicate the IBC Item Number from Table 721.2(2).
11. Sheet A6; Section 11: Please provide plywood sheathing and nailing as required per the structural calculations.
12. Sheet A6 (Section 3); Structural Calculations (Page 7): The calculations indicate the footing reinforcement to be #4 @ 8" o.c. (minimum 3), while the Section 3 indicates 2-#4 each way. Please coordinate.
13. Structural Calculations; Page 2: Please revise the Wind and Seismic Bracing Design from the 2018 IRC to the 2018 IBC. Provide the structural calculations for the lateral analysis.
14. General: Please provide written responses to all review comments.
11/22/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM08601
5326 E Pima St – C-1
Multi-Family – Mixed Use

TRANSMITTAL: November 22, 2021
This site is located in the C-1 zone (UDC 4.7.20). Mixed use is allowed in the zone.

1. The building plans have been reviewed for compliance with DP21-0120 and although it appears that the plans match until DP21-0120 has been approved Zoning cannot approve the building plan.

2. The development package sheets provided in the building set either need to be the stamped approved sheets, marked for reference only or removed from the building plans.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
11/22/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
11/24/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical review comments and provide a written response.

1 .This project falls under commercial review. Please revise all the electrical code references to the IRC to 2017 NEC.

2 . Provide full compliance with the 2018 IECC for the lighting.

3 . Provide AFCI protection for branch circuits as required per art 210 NEC.

4. Provide GFI protected receptacles for all kitchen counter receptacles. NEC 210.

5 . Revise the electrical load calculations for the hot water heaters and the heat pump units. See Mechanical and plumbing plans equipment schedules for actual power requirements.

6 . Provide complete panel schedules. Show voltage, amp, AIC ratings, loads in KVA, amps and balance loads for A and B buses.

7 . Indicate secondary service conductor sizes and types in the line diagram.

8 . Provide a complete luminaire schedule.

9 . Ref; Outdoor Lighting Calculations; (a) Indicate Lighting Area and Option used for lumen calculations per table 401.1 OLC. (b) Use the total parcel size in acres for calculating total Shielded and Unshielded allowable lumens. (C) Include a complete inventory of all the exterior luminaires in the parcel including existing if applicable for the total lumen calculations and indicate allowable lumens vs proposed total lumens, shielded and unshielded.. (d) Indicate exterior lamp color temperature output and compliance with section 402.1 OLC. (e) Indicate whether or not a special inspection is required. Section 104.2.2, 106.2 OLC.

Ref; 2018 IBC sec. 107.2.1, 2017 NEC, 2018 IECC, 2012 Tucson/Pima County Outdoor Lighting Code OLC, City of Tucson Commercial Plan Submittal Requirements.
12/01/2021 IMONSHI1 ENGINEERING REVIEW Passed
12/06/2021 JPEELDA1 FIRE REVIEW Reqs Change Plans show that the building is an R-2. Plans shall indicate that fire sprinklers shall be installed. Fire alarm system shall be installed. FACP to be powered from an "Owners" panel and not one in any of the units.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033

Final Status