Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM08600
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/09/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 11/09/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/12/2021 | GPENNIN1 | ZONING | REVIEW | Approved | |
| 11/12/2021 | GPENNIN1 | ENGINEERING | REVIEW | Passed | |
| 11/12/2021 | GPENNIN1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 11/16/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 11/17/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A3; Wall Legend; Detail 1: The Wall Legend indicates new walls as 3 5/8" 25 ga. metal stud walls at 16" o.c., while the Interior Partition Detail 1 indicates 3 5/8" 20 ga. metal studs at 24" o.c. Please coordinate. 2. Sheets A3 and A4; Floor/Furniture Plans: Please revise the elevation indicator sheet number reference in the restroom from 1 to A7. 3. Sheet A5; Ceiling Plan: Please indicate the exit lighting at the north wall exit. 4. General: Please provide written responses to all review comments. |
| 11/22/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 12/01/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |