Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2021 SBLOOD1 ENGINEERING REVIEW Passed
11/10/2021 NMARTEL1 ZONING REVIEW Approved
11/30/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM08586

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FLOOR PLAN:

Provide a floor plan showing each room with labeled function and dimensions. Show proposed door locations and window sizes with type identified as XO or SH.

SECTIONS - DETAILS:

1 Provide a proposed wall detail showing a minimum 12” x 12” foundation with #4 bear reinforcement in CMU walls and foundation. Show furred and insulated interior walls.
2 An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF.
PLUMBING PLANS:

1. Show plumbing drainage and vent (VTR) sizes consistent with Table P3107.3. Update the 2” drain from the water closet.

MECHANICAL PLANS:

Provide heating facilities in all habitable rooms, R303.10. Provide equipment details showing code compliant components, locations and sizes. Provide a Manual J report identifying cooling demand for new units.

ELECTRICAL PLANS:

Provide proposed wiring details showing code compliant device locations and circuit sizes. Show circuit number and size for proposed wiring. Receptacle, lighting and smoke detector circuits require arc-fault protection.

Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details minimum (R-13 walls and R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better.

If you have any questions, please contact: