Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM08585
Parcel: 10510059C

Address:
4267 N 4TH AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM08585
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2021 JVINCEN1 FIRE REVIEW Approved
11/17/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM08577-8585

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. The Earthquake Design data shown on Structural Drawing S0.0 doesn’t match with Design Criteria used on Structural Calculations. Verify and make revisions as needed.
2. The Structural Calculations submitted (Enercalc) references IBC 2015. Resubmit all calculations revised per IBC 2018.
3. Provide Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1

BUILDING REVIEW COMMENTS:
Denied
1. Provide occupant load for the entire project.
2. Sheet A1.0: The project data box indicates a building type A that doesn't exist in the project. Please remove this information.
3. Provide detailed accessible route drawings throughout the entire site that clearly indicate an accessible route from site entry to every building. Provide all applicable unit plans and details.
4. The building with the leasing office contains a mix use condition. Indicate on the plans what mix use approach is being utilized and correlate and applicable requirements in accordance with Section 508 and Table 508.4.
5. Draftstopping is required in the floor and ceiling spaces in accordance with Section 708.4.2.
6. Sheet A2.21: Remove all reference to a building type A if not being used in the project.
7. Sheet A5.01: Remove all details and references to building type A.
8. Sheet A9.01: Remove references to building type A in the door and window schedule.3
9. Sheet A10.01: Remove references to building type A in the wall schedule.

MECHANICAL REVIEW COMMENTS:
Denied
1. Provide mechanical plan for pool mechanical room and provide any chemicals being used and stored and quantities and any heating equipment being used (IMC2018,106.3.1)

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E1.03 SITE LIGHTING PHOTOMETRICS: Comment and calcs meet exterior lighting requirements. No electrical issues
E3.03 ENLARGED UNIT 2 ELECTRICAL PLAN: Comment only on Note #2. Do you really want to use Aluminum for the range circuit? No electrical issues

PLUMBING REVIEW COMMENTS:
Denied
1). Plan page A5.01 only shows 10.5 to 12" from sidewall to lavatory center. The minimum requirement is 15" See details #15 & #22 -IPC 405.3.1
2). Supply the site/civil site utility piping plan to see that the Building water & sewer stub outs correlate with the continuation of the water service & sewer. -IPC 106.3.1
3). Update plan pg. P3.0 to show complete sanitary waste & water riser diagrams that correlate with plan pages P1.1 & P1.2. A106.3.1
4). Lease Office Lav-1 on plan pg. P4.1 needs ASSE 1070 mixing valve. -IPC 419.5
5). WC-1 on plan pg. P4.1 needs to be ADA type. -IPC 404.1 404.2
6). Plan pg. P4.1 fixture schedule needs to include manufacturer names & model numbers. -IPC A106.3.1
7). Gas piping shown in notes #15,16,18 on plan pg. P4.1, but not illustrated throughout plan set. -IFGC A106.3.1 (if no gas remove notes)
8). Note# 17 on plan pg. P4.1 notates fire system, fire system isn't illustrated, is the fire system supplied by the potable water? if yes add illustrations & information. to plumbing plans -IPC A106.3.1 IPC 608
11/22/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM08577, T21CM08578, T21CM08579, T21CM08580, T21CM08581, T21CM08582, T21CM08583, T21CM08584, T21CM08585
4267 N 4th Ave – R-2
Multi-Family (1st Review)

TRANSMITTAL: November 22, 2021
This site is located in the R-2 zone (UDC 4.7.9). A multi-family is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Zoning has reviewed the building plans for compliance with DP21-0216 and although it appears that the buildings matches what is shown on the DP, until the DP is approved Zoning cannot approve the building plans.

2. Ensure that all site details match what has been submitted on the DP.

3. Provide a detailed breakdown that clearly shows how many of each type unit along with the floor area so that impact fees can be correctly assessed.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
11/22/2021 ROBERT SHERRY WATER REVIEW Completed
11/22/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
12/08/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2021 VVERA1 OUT TO CUSTOMER Completed