Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM08563
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/03/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 11/09/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/09/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 11/09/2021 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 11/15/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/22/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 11/22/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/22/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/01/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 . Please verify compliance with NEC requirements for overcurrent protection at 125%. It appears the load calculations and OCPD’s do not reflect this. NEC 625.41 Ref; 2018 IBC sec 107.2.1, 2017 NEC, |