Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comment and provide a written response.
1. Where does the 17' foot overhead service conductors clearance requirement come from? The NEC service conductor clearances from grade are, "10ft", "12ft", "15ft", "18ft", "24ft". NEC 230.24B.. Revise the clearance requirement to the applicable distance and re- submit.
Ref; 2017 NEC.