Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM08520
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/30/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comment and provide a written response. 1. Where does the 17' foot overhead service conductors clearance requirement come from? The NEC service conductor clearances from grade are, "10ft", "12ft", "15ft", "18ft", "24ft". NEC 230.24B.. Revise the clearance requirement to the applicable distance and re- submit. Ref; 2017 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/30/2021 | VVERA1 | OUT TO CUSTOMER | Completed |