Permit Number: T21CM08491
Parcel: 140290620

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM08491
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2021 SBLOOD1 ENGINEERING REVIEW Passed
11/09/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/09/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the envelope compliance certificate to correspond to the proposed changes to the building envelope (e.g. furring in exterior wall, adding R-38 insulation to roof).
2. Revise the mechanical compliance certificate using Table CC403.3.2 (2), IECC 2018. The specified heat pumps are not packaged terminal heat pumps.
3. The HVAC load analysis shows a total load of 7.91 tons of cooling for the warehouse, but the plans call for four 5-ton HVAC units. How is this justified? Reference: SectionsC403.1.1 and C502.2.3, IECC 2018.
4. Show the size, routing, and termination of the condensate drains for the HVAC units. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
11/09/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/09/2021 ROBERT SHERRY WATER REVIEW Completed
11/16/2021 JPEELDA1 FIRE REVIEW Approved
11/19/2021 STEVE SHIELDS ZONING REVIEW Approved
11/19/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/23/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved