Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM08451
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/15/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. The electrical load summary shows Panel ‘L1’. The panel schedule and power plans calls the panel ‘CC’. Is this the same panel? Please clarify. 2. EV loads are to be calculated as continuous (125%). Please revise load and overcurrent, feeder sizes, calculations to comply with NEC art’s 625.41, 625.42 Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |