Permit Number: T21CM08451
Parcel: 13319195A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM08451
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM08451
6700 E Speedway Blvd. – O-1
Install Vehicle Charging Stations (1st Review)

TRANSMITTAL: November 3, 2021
This site is located in O-1 Zone (4.7.13) Administrative Office is an allowed use in the zone (Table 4.8-3), subject to Use Specific Standards 4.9.4.R and 4.9.13.J.

1. Provide a site plan that clearly shows that the proposed charging stations do not encroach into vehicle parking spaces or the associated vehicle overhang area or into a pedestrian circulation path.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
11/03/2021 JPEELDA1 FIRE REVIEW Approved
11/08/2021 SBLOOD1 ENGINEERING REVIEW Approved
11/16/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/16/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/23/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements