Review Details: RESUBMITTAL
Permit Number - T21CM08401
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/15/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 12/22/2021 | NMARTEL1 | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL Nicholas Martell, Planner T21CM08401 Commercial Shade Structures December 22, 2021 The commercial plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed. Please resubmit the plans with a detailed response letter addressing the following: 1. The following comment was not addressed on the most recent submittal: "Please add exterior elevation drawings for the shade structures." Please show the elevation drawings with full measurements. 2. The following comment was not addressed on the most recent submittal: "Add the setback dimensions of the proposed shade structures" Elevation and setback measurements are required. Refer to the following template: https://www.tucsonaz.gov/files/pdsd/pdfs/Addition_Sample.pdf Addressing the template above, please see page 2 to see how setback distances from the property line are shown on the site plan. Additionally, see page 4 as an example of how to draw elevations measurements. It appears that the same plans may have been resubmitted, as the zoning comments were not addressed. Please resubmit the corrected plans and contact me when they are resubmitted. If you have any questions about this transmittal, please contact me at nicholas.martell@tucsonaz.gov |