Permit Number: T21CM08400
Parcel: 12402023B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM08400
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2021 SBLOOD1 ENGINEERING REVIEW Passed
11/05/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: A site plan is required, indicating the location of the building. Use the IBC Section 107.2.6 for requirements.
2. General: Provide the scope of work for this project on the site plan sheet. Use the IBC Section 107.2.1 for requirements.
3. General: Provide a code analysis (occupancy classification, construction type, square footage) for the building. Use the IBC Section 107.1 for requirements.
4. General: Provide a detail on the documents indicating how the new shelving is attached to the existing floor slab.
5. General: Please provide written responses to all review comments.
11/08/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/08/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/08/2021 ROBERT SHERRY WATER REVIEW Completed
11/15/2021 STEVE SHIELDS ZONING REVIEW Reqs Change Clarify what the propose use is.
11/15/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/18/2021 JVINCEN1 FIRE REVIEW Reqs Change See building comments.
11/23/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed