Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM08400
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/01/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 11/05/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: A site plan is required, indicating the location of the building. Use the IBC Section 107.2.6 for requirements. 2. General: Provide the scope of work for this project on the site plan sheet. Use the IBC Section 107.2.1 for requirements. 3. General: Provide a code analysis (occupancy classification, construction type, square footage) for the building. Use the IBC Section 107.1 for requirements. 4. General: Provide a detail on the documents indicating how the new shelving is attached to the existing floor slab. 5. General: Please provide written responses to all review comments. |
| 11/08/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 11/08/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/08/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/15/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | Clarify what the propose use is. |
| 11/15/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/18/2021 | JVINCEN1 | FIRE | REVIEW | Reqs Change | See building comments. |
| 11/23/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed |