Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM08393
Parcel: 13733909A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM08393
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2022 LOREN MAKUS ENGINEERING REVIEW Approved
11/09/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM08393

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. Structural steel, components and fasteners for the roof screen are to be protected against corrosion in accordance with AISC 360 Section B.13 as indicated in IBC 2018 Section 2203.1.
2. Designer is to coordinate venting and drainage hole requirements for HSS tube members that are galvanized using the hot-dip galvanizing process. Provide for plugs as needed. AWS D-19.0 calls for welds on galvanized steel to be free of zinc. Field welds on galvanized parts requires the removal of the zinc coating in the area of weld. Provide zinc paint (approved by the galvanizer) and apply as required to the weld and steel area to provide protection.
3. Roof drainage and secondary drains are to comply with IBC 1502.1.
4. Non-load bearing walls require a deflection track or details to allow for the relative lateral deflection of the structural members.
5. Architectural Drawings show a drive thru canopy on the west side of the building. No structural info is shown on the Structural drawings. Verify and provide info.
6. Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.

BUILDING REVIEW COMMENTS:
Denied
1. The occupant load factor used for the business area is incorrect. The occupant load factor for business is 150. Please recalculate and update the occupant load.

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved
11/09/2021 ROBERT SHERRY WATER REVIEW Reqs Change Provide the civil utilities drawings referenced on the plumbing drawings to show the installation of the water service and other site utilities. Reference: Sections 107.2.1 and 107.2.6, IBC 2018.
11/17/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM08393
1830 W Valencia Rd – C-2
New Food Service – DP21-0189 – (1st Review)

TRANSMITTAL: November 17, 2021

This site is located in the C-2 zone (UDC 4.7.21), Food Service is an allowed use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 and 4.9.13.P.

1. Zoning has reviewed this building plan for compliance with DP21-0189 and although it appears that the floor plans and elevations match Zoning cannot approve the building plans until the DP has been approve. Also it does not appear that the bike rack details and dumpster details provided in the building plans match what is shown on the DP.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
11/17/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
11/26/2021 JVINCEN1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/04/2022 VVERA1 OUT TO CUSTOMER Completed