Permit Number: T21CM08373
Parcel: 121041000

Address:
5772 E SENECA ST

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM08373
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2021 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T21CM08373
Roof top Solar Panels (1st Review)
5772 E Seneca St

TRANSMITTAL DATE: December 1 2021



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: Line side taps require compliance with NEC 230.46. Update the plans showing a tap enclosure with sufficient space for the tap device, or show a meter socket extension with tap terminals (approved Milbank tapping device).Verify that the distribution panel has no more than six switches for disconnecting all loads, NEC 230.71.

COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
12/01/2021 VVERA1 OUT TO CUSTOMER Completed