Permit Number: T21CM08371
Parcel: 117200270

Address:
260 S CHURCH AV

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T21CM08371
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/03/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/03/2021 ROBERT SHERRY WATER REVIEW Passed
11/04/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.00; Site Plan: No information is provided for the Ticket Booth, Skate Rental, or Skate Storage structures. Please provide architectural details and plans as required. In addition, provide structural details, plans, and calculations as required for those structures.
2. Sheet A1.00; Site Plan: In Keynote 7, please indicate the fence material and height. Fences greater than 7' in height require details on the drawings.
3. Sheet A1.00; Site Plan: Please indicate on this sheet the deck material and details as required.
4. Sheet A1.00; Site Plan: Please indicate on this sheet the concrete support slab requirements for the chiller (Keynote 14), the generator (Keynote 15), and fuel storage (Keynote 16). Indicate slab thicknesses and details as required.
5. General: Please provide written responsis to all review comments.
11/17/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/18/2021 STEVE SHIELDS ZONING REVIEW Passed
11/18/2021 SSHIELD1 ENGINEERING REVIEW Passed
11/26/2021 JVINCEN1 FIRE REVIEW Reqs Change -See building comments.

John Vincent
john.vincent@tucsonaz.gov
5207914502

Final Status

Task End Date Reviewer's Name Type of Review Description
11/26/2021 VVERA1 OUT TO CUSTOMER Completed