Permit Number: T21CM08343
Parcel: 12009308A

Address:
4823 S 6TH AV 15

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T21CM08343
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2021 ANY ZONING REVIEW Active
10/22/2021 ANY ENGINEERING REVIEW Active
10/22/2021 ANY ELECTRICAL-COMMERCIAL REVIEW Active
10/22/2021 ANY COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
11/01/2021 ROBERT SHERRY WATER REVIEW Completed
11/01/2021 JPEELDA1 FIRE REVIEW Approved
11/02/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change This activity eliminates six water closets, two urinals and six lavatories from building 15. Provide calculations to show that the contestants, wranglers, and the occupants of four sets of bleachers located east of the arena will have adequate plumbing facilities within 500-feet. Reference: Sections 403.1 and 403.3.3, IPC 2018.
11/02/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide locking access port caps for the condensing units per Section 1101.10, IMC 2018 or locate the condensing unit in a controlled space.
11/02/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-1 (Demolition Floor Plan); Sheet A-1 (Proposed Floor Plan): The Demolition Floor Plan indicates 8 existing water closets, 2 existing urinals, and 6 existing lavatories in the restroom area to be removed. The Proposed Floor Plan indicates 2 new water closets and 2 new lavatories are to replace the removed fixtures. From the Site Plan on Sheet SD-1, it appears these restrooms could serve occupants not only in the Committee Building, but also from the bleachers, animal pens, Press Media Building, Staging Area, and Lion's Building. Please verify with calculations on the drawings the plumbing fixtures provided in this building meet the requirements of the IBC Table 2902.1 and Section 2902.3.3 for water closets and sinks in this area.
2. Sheet A-1; Wall Legend: For New Walls (Interior), please indicate the metal stud gauge required.
3. Sheet A-1; Wall Legend: The New Walls (Interior) reference Details 5/A2 and 6/A2. Please revise those references.
4. Sheet A-1; Proposed Floor Plan: A section cut on the west wall at the work counter references 6/A2. Please revise that reference.
5. General: Please provide written responses to all review comments.