Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM08336
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/16/2021 | PCAMARE1 | OIP | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Residential Review Section PROJECT: T21CM08336 Roof top Solar Panels (1st Review) 2784 W CALLE DE DALIAS TRANSMITTAL DATE: November 16, 2021 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments COMMENT: Provide an appropriate Maximum Photovoltaic System Voltage (Vpp x 1.14) NEC 690.7 and Table 690.7 (16 degrees F lowest ambient). Show a collector module design with a corrected voltage maximum not exceeding 600 volts. COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans . |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/16/2021 | VVERA1 | OUT TO CUSTOMER | Completed |