Permit Number: T21CM08317
Parcel: 11301146Z

Address:
1785 E PRINCE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM08317
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/28/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify that the relocated lavatory will have a metering faucet. The metering faucet shall dispense a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09 [Initial comment: Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference, Section 107.2.1, IBC 2018, Sections 303.2, 419.6, 607.1.2, IPC 2018 as amended by the City of Tucson, and Section C404.5, IECC 2018.]
12/28/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed