Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM08317
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/01/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/01/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the mechanical air distribution system to ensure that adequate ventilation will be provided for all the occupied spaces (e.g. rooms 101, 103 and 106). Reference: Section 403.3.1.1, IMC 2018. 2. Revise the mechanical design as required to avoid using the corridor, west of rooms 102 and 103, as a return air duct. Reference: Section 601.2, IMC 2018. |
11/01/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference, Section 107.2.1, IBC 2018, Sections 303.2, 419.6, 607.1.2, IPC 2018 as amended by the City of Tucson, and Section C404.5, IECC 2018. |
11/01/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
11/01/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
11/12/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
11/12/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
11/17/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/26/2021 | JVINCEN1 | FIRE | REVIEW | Approved |