Permit Number: T21CM08317
Parcel: 11301146Z

Address:
1785 E PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM08317
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/01/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the mechanical air distribution system to ensure that adequate ventilation will be provided for all the occupied spaces (e.g. rooms 101, 103 and 106). Reference: Section 403.3.1.1, IMC 2018.
2. Revise the mechanical design as required to avoid using the corridor, west of rooms 102 and 103, as a return air duct. Reference: Section 601.2, IMC 2018.
11/01/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference, Section 107.2.1, IBC 2018, Sections 303.2, 419.6, 607.1.2, IPC 2018 as amended by the City of Tucson, and Section C404.5, IECC 2018.
11/01/2021 SBLOOD1 ENGINEERING REVIEW Passed
11/01/2021 ROBERT SHERRY WATER REVIEW Completed
11/12/2021 STEVE SHIELDS ZONING REVIEW Approved
11/12/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/17/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/26/2021 JVINCEN1 FIRE REVIEW Approved