Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM08224
Parcel: 128100530

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM08224
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/28/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/28/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/28/2021 ROBERT SHERRY WATER REVIEW Completed
11/04/2021 IMONSHI1 ZONING REVIEW Approved
11/04/2021 IMONSHI1 ENGINEERING REVIEW Passed
11/04/2021 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
11/16/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide full compliance with the 2018 IECC for the lighting.
11/26/2021 JVINCEN1 FIRE REVIEW Approved